VERYPOWER® Generating sets are highly professional equipment, the maintenance should be carried out by qualified technician. As the professional manufacturer and service provider, VERYPOWER have a skilled service team to provide long-terms regular maintenance service to our customer
product | Daily or weekly | Every 250 hours | Every 500 hours | Every 1500 Hour or year | Every 4500 Hour or two years | Once a year |
Check - battery charging system | ![]() | ![]() | ![]() | ![]() | ![]() | |
Check - battery electrolyte liquid level, electrolyte specific gravity | ![]() | ![]() | ![]() | ![]() | ![]() | ![]() |
Check - tighten the battery terminals and apply grease to the terminals and terminals | ![]() | ![]() | ![]() | ![]() | ||
Cleaning - electromagnetic sensor (if fitted) | ![]() | ![]() | ||||
Check - Safety and alarm controller operation | ![]() | ![]() | ||||
Check - signal cable wiring and fastening (if loose) | ![]() | ![]() | ![]() | ![]() |
product | Daily or weekly | Every 250 hours | Every 500 hours | Every 1500 Hour or year | Every 4500 Hour or two years | Once a year |
Check the oil tank oil, add the appropriate grade and type of oil | ![]() | ![]() | ![]() | ![]() | ![]() | ![]() |
Check - control tank oil, add the appropriate grade and type of oil | ![]() | ![]() | ![]() | ![]() | ![]() | |
Check - Leakage | ![]() | ![]() | ![]() | ![]() | ![]() | ![]() |
Inspection - Oil preheater operation (if fitted) | ![]() | |||||
Replacement - oil filter | ![]() | ![]() | ![]() | ![]() | ![]() | |
Replacement - oil filter (if fitted) | ![]() | ![]() | ![]() | ![]() | ![]() | |
Replacement - engine shell oil | ![]() | ![]() | ![]() | ![]() |
Daily
Check whether there is leakage for fuel, coolant and Lub. oil
Check coolant preheater, engine starting will be failed if temperature is too low
Check battery charger
Weekly maintenance
Check the liquid level of lube and coolant
Check battery charger
Monthly maintenance
Check the air resistance value of air filter
Check the genset and confirm whether there are unusual vibration, excessive exhaust, leakage of noise, coolant and fuel. The engine component will be lubricated by regular test running to enhance the reliability of starting. Preventing Oxidization of connection terminal should be prevented. Avoiding the fuel degeneration. 2tines Running for 10-15 minutes at no load everymonth.
Check whether there is leakage or connnection looseness.
Check the fuel level and condition of transit pump.
Check whether there is leakage or over-resist in exhaust system, discharge the condensation liquid.
Check battery connecting condition, charge the battery when the specific gravity is lower than 1.26.
Check the vent resistance of air inlet, check whether the maintenance kit are prepared.
Semi-annual maintenance
Check the lub. oil and bypass filter
Clean or replace ventilation filter of crankcase
Discharge sediment of fuel tank, check whether there is any damage on fuel pipe electric control and alarm system
Clean the grease, lube, dust and sediment on generating set
Check the contact of power transmission cable, breaker and switch.
Check the start function and performance with rated load by emulate the mains power outage, check the ATS and related configuration.
Annual maintenance
Checking fan in radiator, belt wheel and pump.
Tighten fastening.
Clean the output and control box, check and fasten all the wire connection, measure and record the insulation resistance, check the heater in alternator.
Manual operating to check the main circuit breaker, verifying the auto trip function according to the manual of manufacturer.
The Genset should be run for 4 hours under 5% loading a year at least if the generating set is usually running under no-load or light-load.
Insulation condition should be checked if the machine room had been flooded or too wet. Preliminary testing should be carried out before finally load testing, and take it as benchmark for routine testing.
For standby generating set, it should be maintained thorough for one time annual, including the replacement of lub. oil, lube filter, coolant filter, fuel filter, air filter etc.
Scan code concerns WeChat